The air-lab heat register (WR) is used in ventilation technological appliances and
air flow carrying casings for the pre or reheating of air.
Depending on the respective application use, the heat register is used behind a filter
in the fresh air or incoming air flow.
Heat register for
interim mounting
Heat register for
mounting
Heat register for installation
The air-lab heat register is available in diverse combinations of various widths (1 … 6 zones)
and lengths (1 … 9 chip series).
PTC Register
Models (examples):
i
Connector block for connection to the
power supply
i
Mounting adapter
Version “interim mounting” (fixing hole
with 2-sided dome):
Version „mounting“
(fixing hole with
1-sided dome):
Version “Installation”
(fixing hole
without dome):
i
2 versions for incorporating thermal cutoff adapter and temperature guard
(as required)
i
Series Type
Unit
WR
3x7CT130-U
WR
3x7CT145-U
WR
3x9CT130-U
WR
3x9CT145-U
Length (without connector block)
Width (without connector block)
Height
mm
mm
mm
168
46
15
168
46
15
216
46
15
216
46
15
Volume flow
Performance (TE -10°C)
Performance (TE 0°C)
Pressure loss
m³/h
W
W
Pa
30 … 150
672 … 1.029
611 … 960
7 … 66
30 … 150
809 … 1.262
770 … 1.195
7 … 66
30 … 150
857 … 1.477
835 … 1.385
6 … 49
30 … 150
704 … 1.184
683 … 1.114
6 … 49
Volume flow
Performance (TE 20°C)
Performance (TE 30°C)
Pressure loss
m³/h
W
W
Pa
15 … 55
387 … 645
352 … 570
3 … 15
15 … 55
455 … 780
432 … 720
3 … 15
15 … 55
527 … 934
487 … 854
3 … 12
15 … 55
421 … 731
386 … 662
3 … 12
Series Type
Unit
WR
6x4CT130-V
WR
6x4CT145-V
Length (without connector block)
Width (without connector block)
Height
Volume flow
Performance (TE 20°C)
Pressure loss
mm
mm
m³/h
W
Pa
96
93
15
20 … 100
330 … 900
4 … 37
96
93
15
20 … 100
380 … 1.022
4 … 37
+49 (0) 2764 261 35 - 0