INSTALLATION CARTRIDGE REGISTER

AREAS OF APPLICATION

The air-lab installation cartridge register (EKR) is used in ventilation technological appliances and

air flow carrying casings for the pre or reheating of air.

 

Depending on the respective application use, the EKR is used behind a filter

in the fresh air or incoming air flow.

PRODUCT DESCRIPTION

Installation cartridge register twin design

Installation cartridge register single design

Connector block

INSTALLATION CARTRIDGE REGISTER SINGLE DESIGN (EKR SINGLE)

The air-lab installation cartridge register single model is available in two widths  (7 or 9 chip series).

INSTALLATION CARTRIDGE REGISTER TWIN DESIGN (EKR TWIN)

The air-lab installation cartridge register twin model has the same construction as the previously named installation cartridge register single model.

Two installation cartridge registers single models are connected using H-connectors.

CONNECTOR STRIP

The connector strip is for connecting to the power supply.

The electrical cable line lies outside the air pipe.

TECHNICAL DATA

Series Typee

 

Unit

EKR Single

3x7CT130-U

article no. 70237

EKR Single

3x7CT145-U

article no. 70238

EKR Single

3x9CT130-U

article no. 70227

EKR Single

3x9CT145-U

article no. 70228

Length

 

 

Width

 

 

Height

mm

 

 

mm

 

 

mm

232

 

 

60

 

 

30

232

 

 

60

 

 

30

280

 

 

60

 

 

30

280

 

 

60

 

 

30

Volume flow

 

 

Performance (TE -10°C)

 

 

Performance (TE 0°C)

 

 

Pressure loss

m³/h

 

 

W

 

 

W

 

 

Pa

30 … 150

 

 

672 … 1.029

 

 

611 … 960

 

 

7 … 66

30 … 150

 

 

809 … 1.262

 

 

770 … 1.195

 

 

7 … 66

30 … 150

 

 

857 … 1.477

 

 

835 … 1.385

 

 

6 … 49

30 … 150

 

 

704 … 1.184

 

 

683 … 1.114

 

 

6 … 49

Volume flow

 

 

Performance (TE 20°C)

 

 

Performance (TE 30°C)

 

 

Pressure loss

m³/h

 

 

W

 

 

W

 

 

Pa

15 … 55

 

 

387 … 645

 

 

352 … 570

 

 

3 … 15

15 … 55

 

 

455 … 780

 

 

432 … 720

 

 

3 … 15

15 … 55

 

 

527 … 934

 

 

487 … 854

 

 

3 … 12

15 … 55

 

 

421 … 731

 

 

386 … 662

 

 

3 … 12

Series Typee

 

Unit

EKR Twin

3x7CT130-U

article no. 70242

EKR Twin

3x7CT145-U

 

EKR Twin

3x9CT130-U

article no. 70230

EKR Twin

3x9CT145-U

 

Length

 

 

Width

 

 

Height

mm

 

 

mm

 

 

mm

232

 

 

120

 

 

30

232

 

 

120

 

 

30

280

 

 

120

 

 

30

280

 

 

120

 

 

30

Volume flow

 

 

Performance (TE -10°C)

 

 

Performance (TE 0°C)

 

 

Pressure loss

m³/h

 

 

W

 

 

W

 

 

Pa

60 … 300

 

 

1.344 … 2.058

 

 

1.222 … 1.920

 

 

7 … 66

60 … 300

 

 

1.618 … 2.524

 

 

1.540 … 2.390

 

 

7 … 66

60 … 300

 

 

1.714 … 2.954

 

 

1.670 … 2.770

 

 

6 … 49

60 … 300

 

 

1.408 … 2.368

 

 

1.366 … 2.228

 

 

6 … 49

Volume flow

 

 

Performance (TE 20°C)

 

 

Performance (TE 30°C)

 

 

Pressure loss

m³/h

 

 

W

 

 

W

 

 

Pa

30 … 110

 

 

774 … 1.290

 

 

704 … 1.140

 

 

3 … 15

30 … 110

 

 

910 … 1.560

 

 

864 … 1.440

 

 

3 … 15

30 … 110

 

 

1.054 … 1.868

 

 

974 … 1.708

 

 

3 … 12

30 … 110

 

 

842 … 1.462

 

 

772 … 1.324

 

 

3 … 12

ACCESSORIES

● Connector strip (article no. 70225)








● R-connector (article no. 10283)









● H-connector (article no. 10290)

 

air-lab GmbH

Zum Eulenbruch 10 & 12

D - 57399 Kirchhundem

 

Tel

Fax

 

 

info@air-lab.de

 

+49 (0) 2764 261 35 - 0

+49 (0) 2764 261 35 - 20