The air-lab installation cartridge register (EKR) is used in ventilation technological appliances and
air flow carrying casings for the pre or reheating of air.
Depending on the respective application use, the EKR is used behind a filter
in the fresh air or incoming air flow.
Installation cartridge register twin design
Installation cartridge register single design
Connector block
The air-lab installation cartridge register single model is available in two widths (7 or 9 chip series).
PTC Register
i
4x sockets for connectors
H-connector for attachment in housing grooves (accessories)
Installation example
R-connector or attachment using screws (accessories)
Installation example
i
Connector strip
i
The air-lab installation cartridge register twin model has the same construction as the previously named installation cartridge register single model.
Two installation cartridge registers single models are connected using H-connectors.
PTC Register
i
2x H-connector Connection of 2 installation cartridge registers single to an installation cartridge register twin
i
Connector strip
i
Connector strip
i
PTC Register
i
4x R-connector for mounting using screws
i
The connector strip is for connecting to the power supply.
The electrical cable line lies outside the air pipe.
2x drilling for mounting
Installation example screw connection with housing wall (fixed connector strip)
Installation example screw connection with installation cartridge register („flying“ connector strip):
i
Connection for mains voltage
i
Series Type
Unit
EKR Single
3x7CT130-U
article no. 70237
EKR Single
3x7CT145-U
article no. 70238
EKR Single
3x9CT130-U
article no. 70227
EKR Single
3x9CT145-U
article no. 70228
Length
Width
Height
mm
mm
mm
232
60
30
232
60
30
280
60
30
280
60
30
Volume flow
Performance (TE -10°C)
Performance (TE 0°C)
Pressure loss
m³/h
W
W
Pa
30 … 150
672 … 1.029
611 … 960
7 … 66
30 … 150
809 … 1.262
770 … 1.195
7 … 66
30 … 150
857 … 1.477
835 … 1.385
6 … 49
30 … 150
704 … 1.184
683 … 1.114
6 … 49
Volume flow
Performance (TE 20°C)
Performance (TE 30°C)
Pressure loss
m³/h
W
W
Pa
15 … 55
387 … 645
352 … 570
3 … 15
15 … 55
455 … 780
432 … 720
3 … 15
15 … 55
527 … 934
487 … 854
3 … 12
15 … 55
421 … 731
386 … 662
3 … 12
Series Type
Unit
EKR Twin
3x7CT130-U
article no. 70242
EKR Twin
3x7CT145-U
EKR Twin
3x9CT130-U
article no. 70230
EKR Twin
3x9CT145-U
Length
Width
Height
mm
mm
mm
232
120
30
232
120
30
280
120
30
280
120
30
Volume flow
Performance (TE -10°C)
Performance (TE 0°C)
Pressure loss
m³/h
W
W
Pa
60 … 300
1.344 … 2.058
1.222 … 1.920
7 … 66
60 … 300
1.618 … 2.524
1.540 … 2.390
7 … 66
60 … 300
1.714 … 2.954
1.670 … 2.770
6 … 49
60 … 300
1.408 … 2.368
1.366 … 2.228
6 … 49
Volume flow
Performance (TE 20°C)
Performance (TE 30°C)
Pressure loss
m³/h
W
W
Pa
30 … 110
774 … 1.290
704 … 1.140
3 … 15
30 … 110
910 … 1.560
864 … 1.440
3 … 15
30 … 110
1.054 … 1.868
974 … 1.708
3 … 12
30 … 110
842 … 1.462
772 … 1.324
3 … 12
● Connector strip (article no. 70225)
● R-connector (article no. 10283)
● H-connector (article no. 10290)
+49 (0) 2764 261 35 - 0